- The width of the right of way should be kept as per the provisions of the applicable part / section of the Indian Standard Code of Practice for Design, Installation and Maintenance of Overhead Power Lines (IS: 5613).
- For lines up to 220 kV, IS 5613 (Part 2 / Sec 2) recommends the following right of way widths taking into consideration the theoretical requirement of right of way and transport requirements of maintenance:
Transmission Line Voltage in KV
|
Recommended Width of ROW
|
33
|
15 m
|
66
|
18 m
|
110
|
22 m
|
132
|
27 m
|
220
|
35 m
|
400 (Vertical Configuration)
|
52 m
|
400(Horizontal Configuration)
|
46 m
|
±500 HVDC
|
52 m
|
765 Single Ckt (Horizontal Configuration)
|
85 m
|
765 Single Ckt (Delta/Vertical
Configuration)
|
64 m
|
765 Double Ckt (Vertical Configuration)
|
67 m
|
±800 HVDC
|
69 m
|
1200 Single Ckt (Horizontal
Configuration)
|
89 m
|