Guide for selection of insulator creepage distances to suit polluted conditions

Pollution level
Minimum nominal specific creepage distance(a) (mm/kV)(b)
I–Light
16
II–Medium
20
III–Heavy
25
IV–Very heavy
31

Notes:
  1. For actual creepage distances the specified manufacturing tolerances are applicable (IEC 60273, 60305, 60433 and 60720).
  2. rms value corresponding to the highest voltage for equipment (phase to phase).
  3. In very light polluted areas creepage distances less than 16 mm/kV can be used depending upon service experience. 12 mm/kV seems to be a lower limit.
  4. In cases of exceptional pollution a specific nominal creepage distance of 31 mm/kV may not be adequate. Depending upon service experience and/ or laboratory test results a higher value of specific creepage distance can be used.

electrolyte with moisture from rain or condensation. When the grease becomes saturated with dirt it must be removed and a new coat applied.
Greasing is not recommended for use with anti-fog insulator shed profiles.
The grease tends to get trapped in the grooves on the underside of the shed and bridged by conductive dirt forming on the grease surface thereby reducing the overall insulator creepage distance.
Calculation of specific creepage path
Typical creepage values for either cap and pin insulator strings or post insulators at 132 kV under very heavy pollution, classification IV, would be determined as follows:

Nominal voltage                                           132 kV rms
Rated voltage                                              145 kV rms
Maximum rated voltage phase to phase
Creepage (from Table)                                 31mm/kV
Test creepage distance                                145kV * 31mm/kV = 4495mm
From manufacturer’s details:
Typical substation insulator                          80 kN minimum failing load
Creepage                                                   330mm
Spacing distance                                        127mm
Number of insulators required to provide 4495 mm creepage using cap and pin porcelain string insulators =4495/330 = 13.6. Therefore the minimum total number of insulators per string would be 14. In this case failure of one unit would reduce the creepage distance to 4165 mm, equivalent to an effective value of 28.7 mm/kV @ 145kV-rated voltage. However, at the nominal system voltage of 132 kV the design value is maintained at 31.5mm/kV. Minimum length of suspension insulator string =14 * 127 = 1778mm. Alternatively, 15 insulators per string could be specified in order to maintain the recommended creepage distance at 145kV-rated voltage under a one insulator shed failure condition. This allows full overhead line operation between normal line maintenance outages at the expense of increased overall string length of 1905mm.

5 comments:

  1. Sir what is the basis category to be heavy or medium polluted area?

    ReplyDelete
    Replies
    1. Pollution severity level mainly based on the value of ESDD and NSDD. once you calculate them you can compare them with the IET pre-determine pollution servility level table to find out in which pollution category you area comes in.

      Delete
  2. Transmission Line Overview: Guide For Selection Of Insulator Creepage Distances To Suit Polluted Conditions >>>>> Download Now

    >>>>> Download Full

    Transmission Line Overview: Guide For Selection Of Insulator Creepage Distances To Suit Polluted Conditions >>>>> Download LINK

    >>>>> Download Now

    Transmission Line Overview: Guide For Selection Of Insulator Creepage Distances To Suit Polluted Conditions >>>>> Download Full

    >>>>> Download LINK

    ReplyDelete
  3. PARAFLEX is an ISO 9001:2008 Certified Company that is engaged in manufacturing and supplying the best quality cables and wires. We are manufacturer of ISI Marked cable & wire.

    Paraflex is famous for:

    Top 10 Wire in India
    Best wire industries
    Best brand of wires and cable in India
    Best wire company name
    Best cable company in India

    ReplyDelete
  4. what is creepage distance for 400kV very polluted area?

    ReplyDelete