1.UTS Test on Stranded Conductor
Circles
perpendicular to the axis of the conductor shall be marked at two places on a
sample of conductor of minimum 5 m length between fixing arrangement suitably
fixed on a tensile testing machine. The load shall be increased at a steady
rate upto 50% of minimum specified UTS and held for one minute. The circles
drawn shall not be distorted due to relative movement of strands. Thereafter
the load shall be increased at steady rate to minimum UTS and held for one
minute. The Conductor sample shall not fail during this period. The applied
load shall then be increased until the failing load is reached and the value
recorded.
2.Corona Extinction Voltage Test
The
samples of a bundle of four conductor of 5 m length shall be strung with
spacing of 457 mm between them at a height not exceeding 8.84m above ground.
The sample assembly when subjected to power frequency voltage shall have a
corona extinction voltage of not less than 320 kV (rms) line to ground under
dry condition. There shall be no evidence of corona on any part of the samples.
The test should be conducted without corona control rings. However, small
corona control rings may be used to prevent corona in the end fittings. The
voltage should be corrected for standard atmospheric conditions.
3.Radio Interference Voltage Test
Under
the conditions as specified under (1.2) above, the conductor samples shall have
radio interference voltage level below 1000 microvolts at one MHz when
subjected to 50 Hz AC voltage of 305 kV line to ground under dry conditions.
This test may carried out with corona control rings and arcing horns.
4.D.C.
Resistance Test on Stranded Conductor
On a
conductor sample of minimum 5m length two contact-clamps shall be fixed with a
predetermined bolt torque. The resistance shall be measured by a Kelvin double
bridge by placing the clamps initially zero metre and subsequently one metre
apart. The test shall be repeated at least five times and the average value
recorded. The value obtained shall be
corrected to the value at 200C as per IS:398-(Part-V)-1982. The resistance
corrected at 200C shall conform to the requirements of this Specification.
5.Chemical
Analysis of Aluminium and Steel
Samples
taken from the Aluminium and steel ingots/coils/strands shall be
chemically/spectrographically analysed. The same shall be in conformity to the
requirements stated in this Specification.
6.Visual and
Dimensional Check on Drums
The
drums shall be visually and dimensionally checked to ensure that they conform
to the requirements of this Specification.
7.Visual
Check for Joints, Scratches etc.
drums shall be rewound in the presence of the Owner. The Owner shall visually
check for scratches, joints etc. and that the conductor generally conform to
the requirements of this Specification. Ten percent (10%) drums from each lot
shall be rewound in the presence of the Owner's representative.
8.Dimensional
Check on Steel and Aluminium Strands
The
individual strands shall be dimensionally checked to ensure that they conform
to the requirement of this Specification.
9.Check for
Lay-ratios of Various Layers
The
lay-ratios of various layers shall be checked to ensure that they conform to
the requirements of this Specification.
10.Procedure
Qualification test on welded Aluminium strands.
Two
Aluminium wire shall be welded as per the approved quality plan and shall be
subjected to tensile load. The breaking strength of the welded joint of the
wire shall not be less than the guaranteed breaking strength of individual
strands.
11.Chemical
Analysis of Zinc
Samples
taken from the zinc ingots shall be chemically/ spectrographically analysed.
The same shall be in conformity to the requirements stated in the
Specification.
12.Galvanising
Test
The test
procedure shall be as specified in IEC : 888. The material shall conform to the
requirements of this Specification. The adherence of zinc shall be checked by
wrapping around a mandrel four times the diameter of steel wire.
13.Torsion
and Elongation Tests on Steel Strands
The test
procedures shall be as per clause No. 10.3 of IEC : 888. In torsion test, the
number of complete twists before fracture shall not be less than 16 on a length
equal to 100 times the standard diameter of the strand. In case test sample
length is less or more than 100 times the stranded diameter of the strand, the
minimum number of twists will be proportioned to the length and if number comes
in the fraction then it will be rounded off to next higher whole number. In
elongation test, the elongation of the strand shall not be less than 4% for a
gauge length of 250 mm.
14.Check on
Barrel Batten strength of Drums
The
details regarding barrel batten strength test will be discussed and mutually
agreed to by the Supplier & Owner in the Quality Assurance Programme.