Ground wires are bare conductors supported at the top
of transmission towers. They serve to shield the line and intercept lighting
stroke before it hits the current carrying conductors below. Ground wires
normally do not carry current. Therefore, they are often made of steel. The
ground wires are solidly connected to ground at each tower in transmission and
distribution system.
Details of Earth wire
The galvanized steel earth wire shall generally conform
to the specification of ACSR core wire as mentioned in IS: 398 (Part-II)-1976
except where otherwise specified herein.
Workmanship
All
steel strands shall be smooth, uniform and free from all imperfections, such as
spills and splits, die marks, scratches, abrasions and kinks after drawing and
also after stranding.
The
finished material shall have minimum brittleness as it will be subjected to
appreciable vibration while in use .
The
steel strands shall be hot dip qalvanised and shall have minimum Zinc coating
after stranding, as stipulated in Cl. 1.7, Table 1 of this section of the
Specification. The zinc coating shall be smooth, continuous, of uniform thickness, free from imperfections. The steel wire rod shall be of such quality
and purity that, when drawn to the size of the strands specified and coated
with zinc, the finished strands shall be of uniform quality and have the same
properties and characteristics as prescribed in ASTM designation B498-M.
The
steel strands shall be preformed and post formed in order to prevent spreading
of strands while cutting of composite earth wire. Care shall be taken to avoid damage to
galvanisation during preforming and postforming operation.
To
avoid susceptibility towards wet storage stains ( white rust), the finished
material shall be provided with a protective coating of boiled linseed oil.
Joints
in Wires
There
shall be no joint of any kind in the finished steel wire strand entering into
the manufacture of the earth wire. There shall be no strand joints or strand
splices in any length of the completed stranded earth wire.
Tolerances
The
manufacturing tolerance to the extent of the limits as stipulated in Cl. 1.7,
Table 1 of this section of the Specification only shall be permitted in the
diameter of the individual steel strands and lay length of the earth wire:
Materials
Steel
The
steel wire strands shall be drawn from high carbon steel rods and the chemical
composition shall conform to the requirements as stipulated in Cl. 1.7, Table 1
of this section of the Specification.
Zinc
The
zinc used for galvanising shall be electrolytic High Grade Zinc and shall
conform to the requirements of IS:209.
Standard
Length
The
standard length of the earth wire shall be as stipulated in Cl. 1.7, Table 1
with the specified tolerance on standard length.
Random
length will be accepted provided no length is less than 70% of standard length
and the total quantity of random lengths is not more than ten (10) percent of
the total quantity in each shipment.
Guaranteed
technical particulars
The
guaranteed technical particulars to be adhered by the contractor / manufacturer
are furnished in below:
The basic technical details of the earth wire for all
type kV line are tabulated below:
Voltage Level
(KV)
|
Unit
|
220, 110, 66, 33
|
765, 400, +500
|
+800 HVDC
|
1200
|
No of Continuous Earth wire
|
Nos
|
One
|
Two
|
Two
|
Two
|
Stranding / Wire diameter
|
mm
|
7/3.15
|
7/3.66
|
7/4.5
|
19/3.00
|
Total Sectional Area
|
mm2
|
54.55
|
73.65
|
111.33
|
134.24
|
Overall diameter
|
mm
|
9.45
|
10.98
|
13.5
|
15.00
|
Approx. Weight (Kg/m)
|
Kg/m
|
0.428
|
10.98
|
13.5
|
15.00
|
Calculated DC resistance at 20ºC
|
Ohm/km
|
3.375
|
2.5
|
1.66
|
1.5
|
UTS in KN
|
Kn
|
56
|
68
|
106.2
|
139.3
|
Modulus of elasticity
|
Kg/mm2
|
19361
|
19361
|
19330
|
19000
|
Coefficient of linear expansion
|
ºC
|
11.5X10-6
|
11.5X10-6
|
11.5X10-6
|
11.5X10-6
|
Max. allowable temperature
|
ºC
|
53ºC
|
53ºC
|
53ºC
|
53ºC
|
Tests
and Standards
Type
Tests on Earth wire
The
following tests shall be conducted once on a sample/samples of earth wire for
every 500 Kms of production from each manufacturing facility:
Testing
Expenses
The
break-up of the testing charges for the type tests specified shall be indicated
separately.
Bidders
shall indicate the laboratories in which they propose to conduct the type
tests. They shall ensure that the tests can be completed in these laboratories
within the time schedule guaranteed by them.
In
case of failure in any type test the Contractor is either required to
manufacture fresh sample lot and repeat all the test successfully once or
repeat that particular type test three times successfully on the sample
selected from the already manufactured lot at his own expenses. In case fresh
lot is manufactured for testing then the lot already manufactured shall be
rejected. The decision of the Purchaser
in this regard shall be final and binding on Contractor.
The
entire cost of testing for the acceptance and routine tests and tests during
manufacture specified herein shall be treated as included in the quoted unit
price except for the expenses of the inspector/ Owner 's representative.
In
case of failure in any type test, repeat type tests are required to be
conducted, then all the expenses for deputation of Inspector/ Owner's
representative shall be deducted from the contract price. Also if on receipt of
the Contract's notice of testing the Owner's representative/Inspector does not
find ‘materials and facilities’ to be ready for testing, the expenses incurred
by the Owner for re-deputation shall be deducted from the contract price.
Additional
Tests
The
Owner reserves the right of having at his own expenses any other test(s) of
reasonable nature carried out at Contractor’s premises, at site, or in any
other place in addition to the aforesaid type, acceptance and routine tests to
satisfy himself that the materials comply with the Specifications.
The
Owner also reserves the right to conduct all the tests mentioned in this
specification at his own expense on the samples drawn from the site at
Contractor’s premises or at any other test center. In case of evidence of noncompliance, it
shall be binding on the part of Contractor to prove the compliance of the items
to the technical specifications by repeat tests, or correction of deficiencies,
or replacement of defective item all without any extra cost to the Owner.
Sample
Batch For Type Testing
The
Contractor shall offer material for selection of samples for type testing only
after getting Quality Assurance Plan approved from Owner’s Quality Assurance
Deptt. The sample shall be manufactured strictly in accordance with the Quality
Assurance Plan approved by Owner.
The
Contractor shall offer at least three drums for selection of sample required
for conducting all the type test.
The
Contractor is required to carry out all the Acceptance tests successfully in presence
of Owner’s representative before sample selection.
Test
Reports
Copies
of type test reports shall be furnished in at least six copies along with
one original. One copy will be returned
duly certified by the Owner only after which the commercial production of the
material shall start.
Record
of routine test reports shall be maintained by the Contractor at his works for periodic inspection by the Owner 's
representative.
Test
Certificates of tests during manufacture shall be maintained by the Contractor.
These shall be produced for verification as and when desired by the Owner.
Inspection
The
Owner's representative shall at all times be entitled to have access to the
works and all places of manufacture,
where earth wire shall be manufactured and representative shall have full
facilities for unrestricted inspection of the Contractor’s works, raw materials
and process of manufacture for conducting necessary tests as detailed herein.
The
Contractor shall keep the Owner informed in advance of the time of starting and
of the progress of manufacture of earth wire in its various stages so that
arrangements can be made for inspection.
No
material shall be despatched from its point of manufacture before it has been
satisfactorily inspected and tested, unless the inspection is waived off by the
Owner in writing. In the latter case
also the earth wire shall be despatched only after satisfactory testing for all
tests specified herein have been completed.
The
acceptance of any quantity of material shall in no way relieve the Contractor
of any of his responsibilities for meeting all requirements of the
Specification, and shall not prevent subsequent rejection if such material is
later found to be defective.
Test
Facilities
The
following additional test facilities shall be available at the Contractor’s
works :
a)
Calibration of various testing and
measuring equipment including tensile testing machine, resistance measurement
facilities, burette, thermometer, barometer etc.
b)
Standard resistance for calibration of resistance
bridges.
c)
Finished Earth wire shall be checked for
length verification and surface finish on separate rewinding machine at reduced
speed (variable from 8 to 16 meters per minute). The rewinding facilities shall
have appropriate clutch system and free of vibrations, jerks etc., with
traverse laying facilities.
Packing
for Earth wire
The
Earth wire shall be supplied in non-returnable, strong, wooden drums and
provided with lagging of adequate strength, constructed to protect the Earth
wire against all damage and displacement during transit, storage and subsequent
handling and stringing operations in the field. The Contractor shall be
responsible for any loss or damage during transportation handling and storage
due to improper packing. The drums shall generally conform to IS:1778-1980,
except as otherwise specified hereinafter.
The
drums shall be suitable for wheel mounting and for letting off the earth wire
under a minimum controlled tension of the order of 5 kN
The
general outline of the drum for Earth wire shall be as per annexed drawing. The
Contractor should submit their proposed drum drawings along with the bid.
For
Earth wire, two standard length shall be wound on each drum.
For
Earth wire, each strand shall be individually welded to prevent parting of two
lengths at a tension less than 15 kN. The two ends where the first length
finishes and the second length starts, shall be clearly marked with adhesive
tape and no weld should be present outside these marks. The length between the two marks shall be
treated as scrap and will not be taken into account for measurement purposes.
All
wooden components shall be manufactured out of seasoned softwood free from
defects that may materially weaken the component parts of the drums.
Preservative treatment shall be applied to the entire drum with preservatives
of a quality which is not harmful to the earth wire.
The
flanges shall be of two ply construction with each ply at right angles to the
adjacent ply and nailed together. The nails shall be driven from the inside
face flange, punched and then clenched on the outer face. The thickness of each ply shall not vary by
more than 3 mm from that indicated in the figure. There shall be at least 3
nails per plank of ply with maximum nail spacing of 75 mm. Where a slot is cut
in the flange to receive the inner end of the earth wire the entrance shall be
in line with the periphery of the barrel.
The
wooden battens used for making the barrel of the earth wire shall be of
segmental type. These shall be nailed to the barrel supports with at least two
nails. The battens shall be closely butted and shall provide a round barrel
with smooth external surface. The edges of the battens shall be rounded or
chamfered to avoid damage to the earth wire.
Barrel
studs shall be used for the construction of drums. The flanges shall be holed
and the barrel studs shaft be threaded over a length on either end, sufficient
to accommodate washers, spindle plates and nuts for fixing flanges at the
required spacing.
Normally,
the nuts on the studs shall stand protruded of the flanges. All the nails used
on the inner surface of the flanges and the drum barrel shall be counter sunk.
The ends of barrel shall generally be flushed with the top of the nuts.
The
inner cheek of the flanges and drum barrel surface shalI be painted with a
bitumen based paint.
Before
reeling, cardboard or double corrugated or thick bituminous waterproof bamboo
paper shall be secured to the drum barrel and inside of flanges of the drum by
means of a suitable commercial adhesive material. After reeling the earth wire,
the exposed surface of the outer layer of earth wire shall be wrapped with
water proof thick bituminous bamboo paper to preserve the earth wire from dirt,
grit and damage during transport and handling.
A
minimum space of 50 mm for earth wire shall be provided between the inner
surface of the external protective lagging and outer layer of the earth wire.
Each
batten shall be securely nailed across grains as far as possible to the flange,
edges with at least 2 nails per end. The length of the nails shall not be less
than twice the thickness of the battens. The nails shall not protrude above the
general surface and shall not have exposed sharp edges or allow the battens to
be released due to corrosion.
The
nuts on the barrel studs shall be tack welded on the one side in order to fully
secure them. On the second end, a spring washer shall be used.
Outside
the protective lagging there shall be minimum of two binder consisting of hoop
iron/galvanised steel wire. Each protective lagging shall have two recesses to
accommodate the binders.
The
earth wire ends shall be properly sealed and secured on the side of one of the
flanges to avoid loosening of the earth wire layers during transit and
handling.
Marking
Each drum shall have the following
information stenciled on it in indelible ink along with other essential data
a)
Contract/Award letter number.
b)
Name
and address of consignee.
c)
Manufacturer’s name and address.
d)
Drum number
e)
Size of earth wire
f)
Length of earth wire in meters
g)
Gross weight of drum with earth wire &
lagging
h)
Weight of empty drum with lagging
i)
Arrow marking for unwinding
j)
Position of the earth wire ends
k)
Distance between outer most layer of Earth
wire and the inner surface of lagging
l)
Barrel diameter at three locations and an
arrow marking at the location of measurement
Verification
of Earth wire Length
The
Owner reserves the right to verify the length of earth wire after unreeling
atlest ten (10) percent of the drums in a lot offered for inspection.
Standards
The
earth wire shall conform to the following Indian/ International Standards,
which shall mean latest revisions, amendments/changes adopted and published,
unless otherwise in the Specification.
In
the event of the supply of earth wire conforming to standards other than
specified, the Contractor shall confirm in his bid that these standards are
equivalent to those specified. In case of award salient features of comparison
between the standards proposed by the Contractor and those specified in this
document will be provided by the Contractor to establish their equivalence.
Sl No
|
Indian Standards
|
Title
|
International
Standards
|
1
|
IS:209-1992
|
Specification for Zinc
|
BS:3436-1986
|
2
|
IS:398-1990
|
Specification for Aluminium
Conductors for Overhead Transmission Purposes
|
IEC:1089-1991
BS:215-1970
|
3
|
IS:398-1998 Part
II
|
Aluminum Conductor Galvanised Steel
Reinforced
|
BS-215-1970
IEC:1089-1991
|
4
|
IS:398-1996 Part
IV
|
Aluminum Alloy stranded
conductor
|
BS-3242-1970
IEC:1089-1991 ASTM-8399-M86
|
5
|
IS:398-1992 Part
V
|
Aluminium conductor Galvanised Steel
Reinforced for Extra High Voltage(400 KV) and above
|
IEC:1089-1991
BS:215-1970
|
6
|
IS:1778-1997
|
Reels and Drums for Bare
Conductors
|
BS:1559-1949
|
7
|
IS:1521-1991
|
Method of Tensile Testing of Steel
Wire
|
IS06892-1984
|
8
|
IS:2629-1997
|
Recommended Practice for Hot Dip Galvanising of Iron
and Steel
|
|
9
|
IS:2633-1990
|
Method of Testing Uniformity of
Coating on Zinc Coated Articles
|
|
10
|
IS:4826-1991
|
Galvanised coating on Round Steel
Wires
|
IEC:888-1987
BS:443-1969
|
11
|
IS:6745-1991
|
Methods of Determination of Weight of Zinc Coating of Zinc Coated Iron and Steel
Articles
|
BS:433-1969
ISO:1460-1973
|
12
|
IS:8263-1983
|
Method of Radio Interference
Tests on High Voltage Insulators
|
1EC:437-1973
NEMA:107-1964 CISPR
|
13
|
IS:9997-1991
|
Aluminium Alloy Redraw Rods
|
IEC:104-1987
|
14
|
Zinc Coated steel wires for
stranded Conductors
|
IEC:888-1987
|
|
15
|
Hard drawn aluminium wire for overhead line conductors
|
IEC:889-1987
|
The
standards mentioned above are available from: Click Here
Tests
on Earth wire
UTS
Test
Circles
perpendicular to the axis of the earth wire shall be marked at two places on a
sample of earth wire of minimum 5 m length suitably compressed with dead end clamps
at either end. The load shall be increased at a steady rate up to 50% of UTS
and held for one minute. The circles
drawn shall not be distorted due to relative movement of strands. Thereafter
the load shall be increased at steady rate to 100% of UTS and held for one
minute. The earth wire sample shall not fail during this period. The applied load shall then be increased
until the failing load is reached and the value recorded.
D.C.
Resistance Test
On
a earth wire sample of minimum 5m length two contact clamps shall be fixed with
a predetermined bolt torque. The
resistance shall be measured by a Kelvin double bridge by placing the clamps
initially at zero meter and subsequently one meter apart. The test shall be
repeated at least five times and the average value recorded. The value obtained shall be corrected to the
value at 200C. The resistance corrected at 200C shall conform to the
requirements of this Specification.
Chemical
Analysis of Zinc
Samples
taken from the zinc ingots shall be chemically/ spectrographically analysed.
The same shall be in conformity to the requirements stated in the
Specification.
Chemical
Analysis of Steel
Samples
taken from the steel ingots/coils/strands shall be chemically,/spectrographically
analysed. The same shall be in
conformity to the requirements stated in this Specification.
Visual
and Dimensional Check on Drums and its barrel strength test.
The
drums shall be visually and dimensionally checked to ensure that they conform
to the requirements of this Specification.
The details regarding barrel strength test will be discussed and
mutually agreed to by Contractor and Owner in the quality assurance programme.
Visual
Check for Joints, Scratches etc. and Length of Earth wire
Ten
percent drums from each lot shall be rewound in the presence of the Owner. The
Owner shall visually check for
scratches, joints etc. and see that the
earth wire generally conforms to the requirements of this Specification. The length of
earth wire wound on the drum shall be measured with the help of counter
meter during rewinding.
Dimensional
Check
The
individual strands shall be dimensionally checked to ensure that they conform
to the requirement of this Specification.
Lay
Length Check
The
lay length shall be checked to ensure that they conform to the requirements of
this Specification.
Galvanising
Test
The
test procedure shall be as specified in IS:4826- 1979. The material shall conform to the
requirements of this Specification. The
adherence of zinc shall be checked by wrapping around a mandrel four times the
diameter of steel wire.
Torsion
Test
The
minimum number of twists which a single steel strand shall withstand during
torsion test shall be eighteen for a length equal to 100 times the standard
diameter of the strand. In case test
sample length is less or more than 100 times the stranded diameter of the
strand the minimum number of twists will be proportioned to the length and if
number comes in the fraction then it will be rounded off to next higher whole
number.
Many thanks for your kind invitation. I’ll join you.
ReplyDeleteWould you like to play cards?
Come to the party with me, please.
See you soon...
คาสิโน
เล่นบาคาร่า
เล่นบาคาร่า
แจกเครดิตฟรี ฝากถอนง่าย